System Highlights

7000 Series Generator Paralleling Control Switchgear
For Mission-Critical and Healthcare Applications

Standard Integrated Features:

  • 115-600V, 3-phase, 4-wire, 100% neutral, 25% copper ground bus,  50/60 Hz, AC system
  • UL 1558 construction, listing and labeling
  • Master control: 12” color touch screen operator interface panel
  • Generator PLC redundancy
  • Two manual paralleling provisions
  • Load control for up to 128 power transfer switches/circuit breakers
  • Load demand and bus load optimization controls
  • No traditional (external) load share components are required
  • Modbus/RTU and Mobus/TCP communications between power transfer switches and SCADA system
  • Event log and historical data trending

Custom Configuration Design Options:

  • Up to 10,000A silver plated main bus with up to 200kAIC bracing level for four cycles
  • Generator breaker frame  size – up to 5000A
  • Enclosure types: NEMA 1; NEMA 3R
  • Bus duct risers up to 6000A
  • Top or bottom conduit entry
  • Unlimited number of engine generators for parallel operation
  • Color touch screen panels for the generator controls
  • Master PLC redundancy:  Hot standby or hot standby synchronized
  • 42-in. LCD graphic display panel – integrated into the switchgear line-up and/or stand alone - wall mounted
  • Two types of the remote annunciation panels available (LED or touch screen type)
  • Remote annunciators available to provide key data at other locations in the building or local campus
  • Any specified circuit breaker brand
  • Electrically and/or manually operated distribution circuit breakers
  • Building management system communications via Modbus/RTU or Modbus/TCP interface 
  • Internet/intranet connectivity via ASCO Terminal Server
  • Extended switchgear warranty – up to 5 years

© Copyright 2001-2009 ASCO Power Technologies, LP