5200 Series Power Manager
Cat. No.: 5220D |
|
|
|
|
|
|
| The ASCO Power Manager is a microprocessor metering device specifically designed for transfer switch applications to provide real-time measurements of single and three phase power systems. It uses digital signal processing technology to measure voltage and phase currents which it uses to calculate real, reactive and apparent power and bi-directional energy.
All measurements are viewed locally or at a remote PC via PowerQuest® or SITEWEBTM products. It can also colect data for both normal and emergency positions using auxiliary contact inputs from the transfer switch. Eight digital input and four digital outputs available for customer use. The ASCO 5200 Series Power Manager is available with or without a stand alone NEMA 1 enclosure.
Direct voltage input for systems up to 600 Volts AC can be monitored without the use of external potential transformers (PTs). Measure 3 phase currents and a fourth current input is available for measuring current in the neutral conductor.
|
|
 |
|
|
|
ASCO 5200D Series Power Manager
|
|
|
|
|
|
Power Metering
- Voltage:
Line - Line: VAB, VBC, VCA, VAVERAGE
Line - Neutral: VAN, VBN, VCN, VAVERAGE
- Frequency: 45.0 to 66.0 Hertz
- Current: IA, IB, IC, IAVERAGE
- Unbalance %: Voltage, Amps
- Real Power: KWA, KWB, KWC, KWNET
- Reactive Power: KVARA, KVARB, KVARC, KVARNET
- Apparent Power: KVAA, KVAB, KVAC, KVANET
- Real Energy: KWHIMPORT, KWHEXPORT, KWHNET
- Reactive Energy: KVARHIMPORT, KVARHEXPORT, KVARHNET
- Power Factor: PFA, PFB, PFC, PFNET
|
|
 |
|
|
|
ASCO 5200 Series Power Manager
|
|
|
|
|
|
Data Access
- Eight digital inputs, four relay outputs.
- Input/Output 15-character, user definable screen display for identification of input/output signals.
|
|
|
|
Optional Configurations and
Connection Arrangements
|
|
Connected To:
|
With Display
|
Without display
|
| Load |
Acc. 85L
|
Acc. 75L
|
| Normal |
Acc. 85N
|
Acc. 75N
|
| Emergency |
Acc. 85M
|
Acc. 75M
|
| Load |
Acc. 85R*
|
Acc. 75R*
|
| Add Suffix "A" to above designations if neutral conductor monitoring is required.
NOTE: Accessory 75 and 85 include component mounting, CTs, shorting blocks and all necessary interwiring.
* Bypass & isolation swicth contacts wired to discrete power manager inputs.
|
|
|
Configurable Designations
- Local - A four line 20 character LCD backlit display.
- Remote - With optional Acc. 72A communication module and Power Manager monitoring systems.
- Provides a user programmable setpoint based on watt demand and can be used to control one of the four relay outputs. Used for peak shaving applications.
|
|
|
|
Integrated ATS Features
- When configured on load of ATS:
- Displays ATS position.
- Displays power data as a function of ATS position (normal/emergency).
- Accumulates energy data separately for normal and emergency sources.
|
|
|
|
|
|
|